UPS SDC3000X-RT

  • Smart On-Line Double Conversion
  • IGBT technology
  • Ability to work with generator
  • Ability to remove EMI and RFI noises
  • High efficiency
  • Equipped with intelligent microcontroller
  • Battery management equipped with switching charger
  • Very low output voltagevariations about ±1%
  • Small Footprint



Technical Specification
Technology

On-Line Double Conversion

Nominal power

3000VA/2100Watt

Efficiency

In normal mode >85%

Transfer time

AC line to back up and vice versa

Charger

Have

Input
Max current

16A

Phase

Single phase

Voltage(VAC)

Full Load: 160~300VAC , Half Load: 110~300VAC

Frequency

50±3Hz

Power factor

Full Load: >0.98

Output
Current

13.6A

Frequency

50±0.25Hz

Phase

Single phase

Nominal power factor

0.7

THD

At linear load <2%

Overload capacity
105% Up to 125% Of nominal power for 1 minutes 
126% Up to150% for 30 sec.
Voltage(AC)

Pure Sine Wave 220VAC±1%

Voltage(Battery)

Pure Sine Wave 220VAC±1%

Battery
Type

Sealed lead acid batteries with free maintenance

Voltage

96VDC

Internal battery

Doesn’t have

Recharge time

Approximately 4~10 hours after 90% discharge

External battery

Equipped with external battery connector

CHARGER CURENT MAX

5.5A

Environment
Temperature

0~40ºC

Altitude

1000 meters max. elevation (Based on IEC 62040)

Audible noise

at 1 meter from surface: <41dB

Humidity

0~80% (Non-condensing)

Dimension[W*D*H] (mm)
With base in order to stand on battery cabinet

102*510*440

Shipping Dimension

205*620*530

With handle

90*540*490

Weight (Kg)
Net weight (Kg)

13.2

Shipping weight (Kg)

15.2

  • Intelligent microprocessor controlled
  • Ability to work with Generator
  • Good Regulation Ability
  • Ability to work in frequencies ±3HZ or ±5HZ
  • Ability to remove EMI and RFI Noises
  • Power Factor Correction
  • System modulated for better and easy Servicing
  • Equipped with External battery connector
  • Low weight and size
  • Includes Switch mode Charger
  • Equipped with Smart RS232 port
  • Includes UPSwing Pro software for controlling and monitoring UPS, auto saving open files and shutdown OS and UPS in critical events
  • Includes Test Button for checking if UPS working properly in lack of AC line Voltage
  • Cold Start
  • Automatically Battery Charging in UPS standby mode
  • Ability to add UPS Device Managers as SNMP Cards
  • Ability to recognize Battery disconnection
  • In Rack-mount models
  • Ability to adjust and control fan's speed
  • Lightning, spike and surge protection (Only in the case of using standard Earth)
  • Protection of UPS Loads against two phased AC line
  • Protection against output Voltage Variations out of range
  • Output Short circuit and overload Protection
  • Protection against Input Voltage and Frequency Variations
  • Over Heat Protection
  • Common Mode Noise Protection
  • Reversed battery connection Protection
  • Charger Short circuit Protection
  • Protection against over-discharge
  • Battery Terminal Short circuit Protection
  • Back Feed Protection on Battery Mode
  • Protection against Upper Battery Charger Voltage
  • Positive back feed Protection
  • Tel/Fax/Modem/Network surge suppression
Audio Alarms
  • Battery Mode (Power Failure)
  • Battery Low
  • UPS Fault
  • High Battery or Charger Voltage in AC Line Mode
  • Over Load
  • Reversed battery connection
  • Going to Sleep or Shutdown mode
  • Testing UPS
  • Site Wiring Fault (Earth & Null)
  • Over Heat
Visual Alarms
  • Battery Mode (Power Failure)
  • AC Line Mode
  • Battery Level Indicators
  • Short circuit and Overload
  • Load Level Indicators
  • Battery Low
  • Input Voltage or Frequency Variations out of range
  • Protection against Over-charge
  • Battery Defect
  • UPS Fault
  • Over Heat
  • Normal Input Voltage
  • By Pass Mode
  • Site Wiring Fault (Earth & Null)
  • Sleep Mode